Commonly Used Electrical Calculation Formulas

classification:

author: Guangyi Substation

source: Guangyi Substation

elease time:2025-04-26

【Summary Description 】 Commonly Used Electrical Calculation Formulas

Commonly Used Formulas

P = U × I R = U ÷ I P – Power (W)

P = I 2 ×R R = P ÷ I 2    R – Resistance (Ω)

P = U 2 ÷R I = U ÷ R I – Current (A)

U = I × R U – Voltage (V)

X C = 1/(2πƒC) X L = 2πƒL X C --- Capacitive Reactance (Ω) X L ---- Inductive Reactance (Ω)

Q L = U 2 / X L Q L =I 2. X L Q L --- Reactive Power (Vr) ƒ----- Frequency (Hz)

Q C = U 2 / X C Q C =I 2. X C Q C --- Reactive Power (Vr)   L-----Inductance

 

Total impedance (Ω) of a series circuit consisting of resistance, inductance, and capacitance

Z = R 2 + (X L –X C ) 2 Z = U ÷ I I = U ÷ Z

 

Motor rated current I N

Three-phase I N = P N 3×U N ×COSΦ×η Single-phase I N = P N ÷U N ×COSΦ×η

P N --------- Motor Rated Power (W) U N ------ Motor Rated Voltage (V)

COSΦ – Power Factor, η – Motor Efficiency

 

Full-voltage motor start

I ST /I N ≤3/4 + P S /4 P S

I ST — Motor starting current (A) I N — Motor rated current (A)

P S — Power transformer capacity (kVA) P N — Motor rated power (kW)

COSΦ = 1 + (Q / P) 2 COSΦ—Power Factor, P—Active Power

Q----Reactive Power

 

Three-phase symmetrical load

△Connection P = 3 × U_phase × I_phase × cosΦ = × U_line × I_line × cosΦ
Y-connection P = 3 × U_phase × I_phase × cosΦ = × U_line × I_line × cosΦ

Determining the Rated Current of Contactor Main Contacts

I = Pn × 10 /K Un Pn Motor Power Un Rated Voltage K ≈ 1–1.4

Ohm's Law:

Series connection: U = U1 + U2 + U3 + U4, R = R1 + R2 + R3 + R4

I = I1 = I2 = I3 = I4

In parallel: U = U₁ = U₂ = U₃ = U₄, I = I₁ + I₂ + I₃ + I₄

1/R = 1/R₁ + 1/R₂ + 1/R₃ + 1/R₄

Two identical resistors connected in parallel: R = R1 × R2 / (R1 + R2)