PRODUCTS CENTER


chad HXGN Box-Type High-Voltage Ring Main Metal-Enclosed Switchgear

The product is suitable for three-phase AC distribution systems ranging from 3 to 24 kV, 50 Hz, and serves as a ring network power supply unit and terminal equipment—specifically, a complete set of high-voltage AC switchgear. It is primarily designed for supplying power at the terminals of 12/24 kV three-phase ring networks or radial grid systems. The device is capable of interrupting load currents and short-circuit currents, as well as making and breaking short-circuit currents. The vacuum load switch used in this system is manufactured by a domestic company.

Product Description

HXGN Box-Type High-Voltage Ring Main Metal-Enclosed Switchgear

I. Product Overview

This product is suitable for three-phase AC distribution systems ranging from 3 to 24 kV and 50 Hz, serving as a ring main unit and terminal equipment in complete high-voltage AC switchgear assemblies. It is primarily designed for supplying power at the terminals of 12/24 kV three-phase ring or radial grid systems, capable of interrupting load currents and short-circuit currents, as well as making and breaking short-circuit currents. The vacuum load switch used in this product is sourced from a domestic Chinese manufacturer.

II. The product complies with the following standards:

GB3906, GB/T16926, GB/T11022, DL/T539, DV/T404

II. Model Meaning

 

III. Operating Environment

1. The ambient air temperature does not exceed 40°C, with a daily average no higher than 35°C; the minimum ambient air temperature is -25°C.

2. The daily average relative humidity does not exceed 95%; the daily average water vapor pressure does not surpass 2.2 kPa; the monthly average relative humidity remains below 90%; and the monthly average water vapor pressure stays under 1.8 kPa.

3. Altitude not exceeding 2000m;

4. Seismic Intensity: 8 degrees; Horizontal Acceleration ≤ 0.4g, Vertical Acceleration ≤ 0.2g;

5. The surrounding air is not noticeably contaminated by dust, smoke, corrosive and/or flammable gases, vapors, or salt spray.

4. Technical Specifications

Serial Number Name Unit Technical Specifications
1 Rated Voltage kV 12 24
2 Rated Insulation Level Lightning Impulse Withstand Voltage kV Alternating and opposing: 75; Break gap: 85 Alternating and opposing: 95; fracture surfaces: 110
1-minute power frequency withstand voltage kV Alternating and opposing: 42; fracture surfaces: 48 Alternating and opposing—55; fracture surfaces—60
3 Rated Current A 630 200 (Vacuum-Powered)
4 Rated Short-Circuit Interrupting Current kA 20, 25 (Load Switch) 31.5 (Load Switch + Fuse Combination Device)
5 Rated Short-Circuit Making Current (Peak) kA 50, 63 (Load Switch) 80 (Load Switch + Fuse Combination Device)
6 Rated Peak Withstand Current kA 50, 63 (Load Switch) 80 (Load Switch + Fuse Combination Device)
7 Rated Short-Time Steady Current   20, 25 (Load Switch) 31.5 (Load Switch + Fuse Combination Device)
8 Thermal Stability Time s 4 2
9 Protection Level IP IP4X, which becomes IP2X when the circuit breaker room door is opened.
10 Busbar System   Single busbar
11 Mechanical Life of Load Switch Next time 5000 (2000 Circuit Breakers)
12 Mechanical Life of Grounding Switch Next time 2000
13 Rated Operating Voltage of Trip and Close Coils V DC220/110, AC220/110
14 Rated Operating Voltage of the Energy Storage Motor V DC220/110

V. Key Features

1. The operating mechanism is a spring-operated type, which can be operated both manually and electrically. The grounding switch and isolating knife are equipped with manual operating mechanisms.

2. The cabinet features an assembled structure with a fully enclosed metal design, achieving a protection rating of IP2X to IP4X.

3. The main components inside the cabinet—vacuum load switches and pneumatic load switches—can be used either individually or in combination with fuses, disconnecting switches, grounding switches, voltage transformers, and current transformers. Additionally, the fuses can be paired with transformers of varying capacities, ensuring they meet diverse operational requirements while effectively interrupting both load currents and short-circuit currents—and even enabling the switching of short-circuit currents.

4. This product can be powered by a ring network, used for terminal power supply, or installed in box-type substations.

5. This cabinet features a simple, lightweight design, is easy to install, and boasts a clear isolation break—making it safe and reliable.