PRODUCTS CENTER
Saint-Lucia XGN Series High-Voltage Box-Type Fixed AC Enclosed Switchgear
Category:
Product Description
XGN Series High-Voltage Box-Type Fixed-Type
Interchangeable Enclosed Switchgear
I. Product Overview
This product series consists of complete sets of AC high-voltage electrical equipment rated for 12 (24) kV and 50 Hz, primarily designed for use in 12–24 kV power supply and distribution systems—including secondary substations, switchgear stations, industrial and mining enterprises, urban residential complexes, airports, railways, tunnels, and high-rise buildings—as well as for transmitting and distributing electrical energy. These devices are also widely employed in civil applications, industrial settings, and distribution automation systems. They feature compact yet expandable metal-enclosed switchgear, with SF6 ring main unit load switchgear incorporating load switches manufactured by ABB, Areva, or domestic companies.
The product meets the following standards:
GB3906, GB/T11022, GB/T16926, DL/T539, DL/T404
II. Model Meaning

III. Operating Environment
1. The ambient air temperature does not exceed 40°C, with a daily average no higher than 35°C; the minimum ambient air temperature is -25°C.
2. The daily average relative humidity does not exceed 95%; the daily average water vapor pressure does not surpass 2.2 kPa; the monthly average relative humidity remains below 90%; and the monthly average water vapor pressure stays under 1.8 kPa.
3. Altitude not exceeding 2000m;
4. Seismic Intensity: 8 degrees; Horizontal Acceleration ≤ 0.4g, Vertical Acceleration ≤ 0.2g;
5. The surrounding air is not noticeably contaminated by dust, smoke, corrosive and/or flammable gases, vapors, or salt spray.
4. Technical Specifications
| Serial Number | Name | Unit | Technical specifications | ||
| 1 | Rated Voltage | kV | 12 | 24 | |
| 2 | Rated Insulation Level | Lightning Impulse Withstand Voltage | kV | Alternating and opposing: 75; Break gap: 85 | Alternating and opposing: 95; fracture surfaces: 110 |
| 1-minute power frequency withstand voltage | kV | Alternating and opposing: 42; Fracture surfaces: 48 | Alternating and opposing: 55; fracture surfaces: 60 | ||
| 3 | Rated Current | A | 630 (125 Load Switch-Fuse Combination Apparatus) | ||
| 4 | Rated Short-Circuit Interrupting Current | kA | 20 (Load Switch) | 31.5 (Load Switch + Fuse Combination Device) | |
| 5 | Rated Short-Circuit Making Current (Peak) | kA | 50 (Load Switch) | 80 (Load Switch + Fuse Combination Device) | |
| 6 | Rated Peak Withstand Current | kA | 50 (Load Switch) | 80 (Load Switch + Fuse Combination Device) | |
| 7 | Rated Short-Time Steady Current | 20 (Load Switch) | 31.5 (Load Switch + Fuse Combination Device) | ||
| 8 | Thermal Stability Time | s | 4 | 2 | |
| 9 | Protection Level | IP | IP4X, which becomes IP2X when the circuit breaker room door is opened. | ||
| 10 | Busbar System | Single busbar | |||
| 11 | Mechanical Life of Load Switch | Next time | 5000 (20,000 Circuit Breakers) | ||
| 12 | Mechanical Life of Grounding Switch | Next time | 2000 | ||
| 13 | Rated Operating Voltage of Trip and Close Coils | V | DC220/110, AC220/110 | ||
| 14 | Rated Operating Voltage of the Energy Storage Motor | V | DC220/110 | ||
Company Address:
No. 9 Qianfeng North Road, Shiji Town, Panyu District, Guangzhou City
Follow us
Copyright © Guangzhou Yibian Electrical Equipment Co., Ltd. Urban sub station Power by 300.cn SEO